Ads 468x60px

Thursday 16 May 2013

UC 27


Ratings:
Industrial (Class H)
100 kVA - 200 kVA (50 HZ)
 
Special Features
Optional Permanent Magnet Generator  (PMG)
system provides constant excitations
under all conditions.
Output winding:12 wire reconnectable.
Optional accessories available for easy paralleling with mains or other generators. Poles : 4
Speed : 1500 or 1800 RPM
Standard 2/3 pitch windings avoid excessive ·AVRS neutral currents. Bearings: Single/Double.
Dynamically balanced rotors, with sealed-for-life ball bearings. AVRS Self Excited:
SX 460 as standard
AS 440 ( optional)
Simple installation and maintenance, with easy access to terminals, rotating diodes and coupling bolts. PMG Excited (Optional):
MX 341 or MX 321
Wide range of flange adaptors and single-bearing disc couplings. Ratings: Industrial (Class H)
100 kVA - 200 kVA ( 50 HZ)
Built to conform with all leading industrial and marine standards.  
Adapters : SAE1/ 2/3
Disc Couplings : SAE 11.5/14
 
 
Ratings:
Three Phase 415 Volts, 1500 RPM, 50 HZ, 0.8 pf ( lag), self excited and self regulated, class H insulation, IP23 Enclosures, Regulation +/- 1%.
KVA FRAME Efficiency @ Full Load & 0.8 pf Gross Weight (kg) Input KW mech. #
1 Bearing 2 Bearing
100 UC2744C* 90.0% 409 422 88.9
110 UC2744D* 90.5% 428 446 97.2
125 UC2744V* 91.0% 448 466 109.9
140 UC2744E* 92.00% 495 509 121.7
160 UC2744F* 92.50% 533 547 138.3
180 UC2744G* 92.50% 583 600 155.6
200 UC2744H* 93.50% 629 643 171.1
 
Single Phase 230 Volts, 1500 RPM, 50 HZ, 0.5 pf ( lag), self excited and self regulated, class H insulation, IP23 Enclosures, Regulation +/- 1%.
KVA FRAME Efficiency @ Full Load & 0.8 pf Gross Weight (kg) Input KW mech. #
1 Bearing 2 Bearing
62.5 UC274C* 84.20% 409 422 59.4
70 UC274D* 85.20% 428 446 65.7
75 UC274E* 86.70% 495 509 76.1
82.5 UC274E* 86.70% 495 509 76.1
100 UC274F* 87.30% 533 547 91.6
125 UC274G* 88.40% 583 643 113.1
Notes:
a) All ratings are based at 40 degrees ambient and 1000 meters altitude.
b) For other ratings and marine applications contact us.
c) Continuous development of our products entitles us to change specification details without notice.
d) # Minimum mechanical power (kw) required from Prime Mover.
* For single bearing machine substitute 1. For double bearing machine substitute 2.

No comments:

Post a Comment