Ratings:
Industrial (Class H)
45 kVA - 82.5 kVA (50 HZ)
 
Special Features
Optional Permanent Magnet Generator  (PMG) system provides constant excitations under all conditions. Output winding:12 wire reconnectable.
Optional accessories available for easy paralleling with mains or other generators. Poles : 4
Speed : 1500 or 1800 RPM
Standard 2/3 pitch windings avoid excessive  neutral currents. Bearings: Single/Double.
Dynamically balanced rotors, with sealed-for-life ball bearings. AVRS Self Excited:
SX 460 as standard
AS 440 ( optional)
Simple installation and maintenance, with easy access to terminals, rotating diodes and coupling bolts. PMG Excited (Optional):
MX 341 or MX 321
Wide range of flange adaptors and single-bearing disc couplings. Ratings: Industrial (Class H)
45 kVA - 82.5 kVA ( 50 HZ)
50 kVA - 100 kVA (60 HZ)
Built to conform with all leading industrial and marine standards.  
Adapters : SAE 2/3/4/1
Disc Couplings : SAE 10/11.5/8/14
 
 
Ratings:
Three Phase 415 Volts, 1500 RPM, 50 HZ, 0.8 pf ( lag), self excited and self regulated, class H insulation, IP23 Enclosures, Regulation +/- 1%.
KVA FRAME Efficiency @ Full Load & 0.8 pf Gross Weight (kg) Input KW mech. #
1 Bearing 2 Bearing
45 UC2244D* 89.00% 287 291 40.4
50 UC2244D* 88.50% 287 291 45.2
55 UC2244E* 89.50% 314 331 49.2
60 UC2244E* 89.00% 314 331 53.9
63 UC2244F* 90.80% 340 351 55.5
70 UC2244F* 90.30% 340 351 62.0
75 UC2244G* 90.90% 384 400 66.0
82.5 UC2244G* 90.50% 384 400 72.9
 
Single Phase 230 Volts, 1500 RPM, 50 HZ, 0.5 pf ( lag), self excited and self regulated, class H insulation, IP23 Enclosures, Regulation +/- 1%.
KVA FRAME Efficiency @ Full Load & 0.8 pf Gross Weight (kg) Input KW mech. #
1 Bearing 2 Bearing
30 UC2244D* 82.50% 287 291 29.1
35 UC2244E* 83.90% 314 331 33.4
40 UC2244F* 84.70% 340 351 37.8
45 UC2244F* 84.60% 340 351 42.6
50 UC2244G* 85.30% 384 400 46.9
55 UC2244G* 85.20% 384 400 51.6
Notes:
a) All ratings are based at 40 degrees ambient and 1000 meters altitude.
b) For other ratings and marine applications contact us.
c) Continuous development of our products entitles us to change specification details without notice.
d) # Minimum mechanical power (kw) required from Prime Mover.
* For single bearing machine substitute 1. For double bearing machine substitute 2.
 